Industry, Nov 2, 2026, 7 min read

A passing check can sit on the wrong side of the break

On October 19 at 22:53 US/Pacific, 06:53 BST on October 20, an underground cable fault cut the one utility feed a data center that hosts Google Cloud's europe-west2-b was using. Google's incident page, revised on November 4, 2026, says both controllers saw voltage on the other feeder, on the supply side of a breaker that had been physically opened. They read it as a healthy source, and neither sent a start command.

The UPS batteries are rated for about five minutes of runtime. Impact started at 23:00 US/Pacific, 07:00 BST on October 20, seven minutes after the fault, when the reserves were used up. Workloads in europe-west2-a and europe-west2-c slowed or failed, because failover landed on them and control planes still called the offline zone.

A passing check can sit on the wrong side of the break. It certifies a path that cannot carry load. The automation then acts on the wrong fact, and the page comes after. Engineers were alerted at 23:04, eleven minutes after the fault and four minutes after impact.

The sensor sat upstream of an open breaker

The facility has two utility paths, A and B, a standby feed for maintenance, and a generator bank behind a pair of controllers. The batteries cover the start of the generators. A quarterly generator load test on October 14 found problems. For the repair, breaker B was physically opened, and feed A carried the hall. On October 19 at 22:53 US/Pacific an underground cable fault took feed A away.

The controllers measured voltage on feeder B, on the supply side of that open breaker. Utility feed B remained energized upstream while its incomer feed was in an open position. The distribution feeds past that breaker were de-energized. The logic did not require both a low voltage and the breaker position. It asked whether voltage was present, got a yes, and did not issue a start command.

The active and standby controllers were running identical control logic. They sensed live voltage from feed B through shared upstream sensors, and that logic read the source as healthy. A remote load transfer was then inhibited for the same reason, the live upstream voltage reading on feed B. People on site moved the hall to the standby utility by a manual transfer. Impact started at 23:00, seven minutes after the fault, when the batteries were used up and the zone's hosts, local storage, and network aggregation lost power. Standby utility power was restored at 23:54.

The other zones paid for the failover

At 23:09, traffic moved toward europe-west2-a and europe-west2-c. The redirected work filled compute there. Admission queues rose. Database failovers slowed. Clients saw intermittent HTTP 500 and 503 errors across the region.

Control planes kept calling metadata and catalog components in the offline zone. Those calls timed out, and job submission stalled. Google says it did not identify impact outside europe-west2. It also says regional services are designed to survive a zone failure, and that in this case unexpected failures caused impact outside that zone. Some Compute Engine failovers were unsuccessful because of capacity limits, and because the storage underneath was hard to replicate.

Power to the data hall was back at 00:20. At 00:50, storage devices with unclean shutdowns began recovery, and responders chose not to restore services that would otherwise make this worse. Controlled traffic returned to europe-west2-b at 03:45. Core platform disruption ended at 04:29. The incident ran 6 hours and 8 minutes, to 05:08 US/Pacific, when 99.5% of Compute Engine virtual machines were operational and healthy. A zone that is dark is a zone problem. A region that cannot absorb that zone, or that still calls it, is a region problem.

A health check restarted instances that were cut off

On September 29, Azure OpenAI, Foundry Agent Service, Foundry Models, and Azure AI services in Sweden Central failed requests and ran slow from 10:03 to 15:58 UTC. The trigger was a deploy. At 09:38 UTC a planned deployment cleared caches during peak traffic. Lookups missed. Two other defects in how that service read its caches sent most lookups through to a backend. By about 10:00, traffic to that backend was about 20 times its normal level.

Connections were held open longer, and client retries added more requests. The nodes ran out of connection capacity, so new outbound connections to the cache and the database could not be opened. At 13:55 UTC Azure confirmed the database layer was healthy.

The long part of the incident was the health check. An instance counted as healthy only if it could connect to the database. A failed check restarted it by design. Restarts removed capacity, and retries put more load on what remained. Adding instances, compute, and memory did not stop it. Existing metrics did not show the connection exhaustion clearly.

At 15:40 UTC they changed the health check so it no longer depended on remote connectivity. The restart loop stopped. Customer impact ended at 15:58 UTC. Monitoring had paged at 10:17 UTC. The check that stretched the incident was already how the service decided an instance was alive. Scaling a restart loop gives you more restarts.

Incident The action needed The check read What followed
Google Cloud, europe-west2, 06:53 BST on October 20 Can this feeder carry the hall? Voltage on the supply side of an open breaker Neither controller sent a start command. The UPS is rated for about five minutes. Impact came seven minutes after the fault. Zones a and c took the failover.
Azure, Sweden Central, September 29 Is this instance dead? Can it connect to the database? Instances restarted. The database was healthy. Scaling did not stop the loop.

Check the sensor before the next page

Take the last failover you trust, and the last health check that is allowed to restart something. Write two lines for each. The first line is the fact the action needs. The second is the fact the sensor reads. Google needed to know the feeder could not carry the hall. The controllers read voltage upstream of breaker B. Azure needed to know the process was dead. The check read a connection to the database.

Then write what a failed check is allowed to do. In Kubernetes, a failed liveness probe makes the kubelet kill the container and start it again. A failed readiness probe takes the pod out of Service traffic and leaves the process up. The docs use readiness when the process depends on an external service and should not be killed. If a liveness handler calls a database or a cache, move that check to readiness. If every pod's readiness calls that same database, they all leave rotation together. That sheds traffic. A restart loop is worse. The probe guide is Configure Liveness, Readiness and Startup Probes.

If maintenance has already dropped you to one path, prove the backup starts inside the battery timer before you stay there. On October 14 a quarterly generator load test found problems, and the site stayed on feed A while breaker B remained open for repair. The November 4 update marks a later generator transfer test, including an automatic start within the battery timer, as completed on October 20 and on October 26. Ask the facility vendor what a planned test, with a way back, would look like before the next window on one path. When a zone fails, watch the survivors, and ask whether a control plane still calls the offline side.

Four questions cover it, for a vendor or for your own platform team.

  1. Where does the sensor sit, relative to the break it is supposed to see?
  2. What is a failed check allowed to do: restart, shed traffic, or only record?
  3. After the last time you ran on one path, did you prove the backup starts inside the battery timer?
  4. During the last zone or dependency failure, did the survivors stay inside their capacity, and did anything still call the offline side?

In London, the errors showed up in zones a and c, which were still up. In Sweden Central, instances restarted after a check that required a database connection, and at 13:55 UTC Azure confirmed that the database layer was healthy. In both cases the cause was what the sensor read, not the first error the page showed.

An investigation that starts from the page will see API errors and job timeouts in London, or instances restarting in Sweden Central. The fact that mattered was what the sensor read when the path failed: voltage on the supply side of an open breaker, or a database connection that could not be opened because the node had no outbound capacity. Dalton is an AI Reliability Platform. It connects code, CI/CD, cloud and observability, builds the map, and does that investigation. It hands you the fix to approve. Every write needs a person's approval.